Amana / AIR-SOURCE HEAT PUMP

AZV7SA2410A*

AZV7SA · source records, page 3

93 published source records · source checked Sep 21, 2026

SEER2 range16–19BTU/Wh
HSPF2 range8.5–8.8BTU/Wh
Cooling capacity23,200BTU/h

Each efficiency range summarizes published EPA records for AZV7SA2410A*. The highest SEER2 and HSPF2 may belong to different combinations. Open a source record below to see its ratings and the scope of its component information.

Model patterns and component strings are preserved exactly. How to read model patterns and combinations →

Heating performance & equipment details

Ranges include the 93 published source records for this model. Values in different rows may describe different configurations. Open an individual record to compare values from the same test configuration.

Reported fieldValue / rangeRecords supplying it
SEER2 · BTU/Wh16–1993 / 93
EER2 · BTU/Wh10.5–1193 / 93
HSPF2 · BTU/Wh8.5–8.893 / 93
Cooling capacity · BTU/h23,20093 / 93
Heating capacity at 47°F / 8.3°C · BTU/h23,20093 / 93
Heating capacity at 17°F / −8.3°C · BTU/h15,80093 / 93
Heating capacity at 5°F / −15°C · BTU/h17,00093 / 93
COP at 5°F / −15°C293 / 93
Equipment / loop typeHP - Split System93 / 93
Refrigerant / source-reported GWPR-32 (GWP:675 | Lower GWP)93 / 93
Compressor stagingContinuously variable93 / 93
Connected capabilityNo · Yes93 / 93

47°F = 8.3°C; 17°F = −8.3°C; 5°F = −15°C. COP is dimensionless. These are reported rating points, not a prediction of a particular home’s heat demand or operating limit.

Manufacturer specifications

These values match the manufacturer’s exact model pattern AZV7SA2410A*. They describe the unit, separately from the EPA system ratings. For electrical work, the specification sheet requires checking the installed unit’s rating plate and its full instructions.

SpecificationValueManufacturer evidence
Equipment weight132 lbAZV7S S-SERIES — product specifications · page 3
Maximum overcurrent protection25 AAZV7S S-SERIES — product specifications · page 3
Minimum circuit ampacity22.4 AAZV7S S-SERIES — product specifications · page 3
Shipping weight147 lbAZV7S S-SERIES — product specifications · page 3
Voltage / phase at 60 Hz208-230/1 V / phaseAZV7S S-SERIES — product specifications · page 3

Matched systems

Each row is one source record. The component column distinguishes listed combinations from outdoor-model ratings without an indoor configuration.

Indoor unit / required furnaceSEER2BTU/WhHSPF2BTU/WhHeating capacity at 5°F / −15°CBTU/hCOP at 5°F / −15°CRecord & comparison
CA*EA3626*3A*+ furnace: A*VT960403BNA*Cold climate designationAHRI reference: 21543405519.008.60170002.00EPA 3625415
CA*EA3626*3A*+ furnace: A*VT960603BNA*Cold climate designationAHRI reference: 21543405619.008.60170002.00EPA 3625416
CA*EA3626*3A*+ furnace: A*VT960803BNA*Cold climate designationAHRI reference: 21543405719.008.60170002.00EPA 3625417
CA*EA3626*3A*+ furnace: A*VT960804CNA*Cold climate designationAHRI reference: 21543405819.008.60170002.00EPA 3625418
CA*EA3626*3A*+ furnace: A*VT961005CNA*Cold climate designationAHRI reference: 21543405919.008.60170002.00EPA 3625419
CHPEA3026*3A*+ furnace: A*VM970603BNA*Cold climate designationAHRI reference: 21543406019.008.60170002.00EPA 3625420
CHPEA3026*3A*+ furnace: A*VM970803BNA*Cold climate designationAHRI reference: 21543406119.008.60170002.00EPA 3625421
CHPEA3026*3A*+ furnace: A*VM970804CNA*Cold climate designationAHRI reference: 21543406219.008.60170002.00EPA 3625422
CHPEA3026*3A*+ furnace: A*VM971005CNA*Cold climate designationAHRI reference: 21543406319.008.60170002.00EPA 3625423
CHPEA3026*3A*+ furnace: A*VS800805CUA*Cold climate designationAHRI reference: 21543406519.008.60170002.00EPA 3625424
CHPEA3026*3A*+ furnace: A*VS800604BUA*Cold climate designationAHRI reference: 21543406419.008.60170002.00EPA 3625425
CHPEA3026*3A*+ furnace: A*VS960603BUA*Cold climate designationAHRI reference: 21543406619.008.60170002.00EPA 3625426
CHPEA3026*3A*+ furnace: A*VS960805CUA*Cold climate designationAHRI reference: 21543406719.008.60170002.00EPA 3625427
CHPEA3026*3A*+ furnace: A*VT800603B*A*Cold climate designationAHRI reference: 21543406819.008.60170002.00EPA 3625428
CHPEA3026*3A*+ furnace: A*VT800604B*A*Cold climate designationAHRI reference: 21543406919.008.60170002.00EPA 3625429
CHPEA3026*3A*+ furnace: A*VT800803B*A*Cold climate designationAHRI reference: 21543407019.008.60170002.00EPA 3625430
CHPEA3026*3A*+ furnace: A*VT800804C*A*Cold climate designationAHRI reference: 21543407119.008.60170002.00EPA 3625431
CHPEA3026*3A*+ furnace: A*VT800805C*A*Cold climate designationAHRI reference: 21543407219.008.60170002.00EPA 3625432
CHPEA3026*3A*+ furnace: A*VT801005C*A*Cold climate designationAHRI reference: 21543407319.008.60170002.00EPA 3625433
CHPEA3026*3A*+ furnace: A*VT960403BNA*Cold climate designationAHRI reference: 21543407419.008.60170002.00EPA 3625434

Sources and documentation

The table uses public EPA ENERGY STAR data. AHRI references are reported by EPA and have not been independently checked with AHRI. Source records do not establish availability, installation suitability or rebate eligibility.

AZV7S S-SERIES — product specificationsManufacturer family specification sheet; only explicitly matched model patterns receive extracted values

Collection method, revision history and known limitations →