PAYNE HEATING AND COOLING / AIR-SOURCE HEAT PUMP

PH8TAN524**AA*

2-STAGE 18 SEER HP · source records, page 4

202 published source records · source checked Sep 21, 2026

SEER2 range15.2–18.5BTU/Wh
HSPF2 range7.8–8.5BTU/Wh
Cooling capacity22,200–25,000BTU/h

Each efficiency range summarizes published EPA records for PH8TAN524**AA*. The highest SEER2 and HSPF2 may belong to different combinations. Open a source record below to see its ratings and the scope of its component information.

Model patterns and component strings are preserved exactly. How to read model patterns and combinations →

Heating performance & equipment details

Ranges include the 202 published source records for this model. Values in different rows may describe different configurations. Open an individual record to compare values from the same test configuration.

Reported fieldValue / rangeRecords supplying it
SEER2 · BTU/Wh15.2–18.5202 / 202
EER2 · BTU/Wh11.5–14202 / 202
HSPF2 · BTU/Wh7.8–8.5202 / 202
Cooling capacity · BTU/h22,200–25,000202 / 202
Heating capacity at 47°F / 8.3°C · BTU/h24,000–25,200202 / 202
Heating capacity at 17°F / −8.3°C · BTU/h14,100–14,900202 / 202
Heating capacity at 5°F / −15°C · BTU/h10,700–11,400202 / 202
COP at 5°F / −15°C1.9–2.24202 / 202
Equipment / loop typeHP - Split System202 / 202
Refrigerant / source-reported GWPR-454B (GWP:470 | Lower GWP)202 / 202
Compressor stagingTwo-stage202 / 202
Connected capabilityNo202 / 202

47°F = 8.3°C; 17°F = −8.3°C; 5°F = −15°C. COP is dimensionless. These are reported rating points, not a prediction of a particular home’s heat demand or operating limit.

Matched systems

Each row is one source record. The component column distinguishes listed combinations from outdoor-model ratings without an indoor configuration.

Indoor unit / required furnaceSEER2BTU/WhHSPF2BTU/WhHeating capacity at 5°F / −15°CBTU/hCOP at 5°F / −15°CRecord & comparison
CAA**2517AM*+ furnace: PG95MSUA36040B**AHRI reference: 21564484617.008.10112002.08EPA 3958106 →
CAA**2517AM*+ furnace: PG96VTAB36060A**AHRI reference: 21564502017.008.10112002.08EPA 3958213 →
CAA**3014AM*+ furnace: PG80VTLB36045A**AHRI reference: 21564522917.008.10109002.06EPA 3958345 →
CAA**3014AM*+ furnace: PG80VTLB36070A**AHRI reference: 21564525517.008.10109002.06EPA 3958362 →
CAA**3017AM*+ furnace: PG80MSUA36040B**AHRI reference: 21564548817.007.80108002.06EPA 3958498 →
CAA**3017AM*+ furnace: PG96VTAB48080B**AHRI reference: 21564608917.008.10110002.06EPA 3958625 →
CAA**3017AM*+ furnace: PG80VTLB36045A**AHRI reference: 21564562617.008.10109002.06EPA 3958695 →
CAA**3017AM*+ furnace: PG80VTLB36070A**AHRI reference: 21564565017.008.10109002.06EPA 3958710 →
CAA**3017AM*+ furnace: PG80VTLB48070B**AHRI reference: 21564566417.008.10110002.06EPA 3958719 →
CAA**3017AM*+ furnace: PG80VTLB48090B**AHRI reference: 21564568717.008.10110002.04EPA 3958732 →
CAA**3017AM*+ furnace: PG95MSUA48060B**AHRI reference: 21564588617.007.80110002.04EPA 3958941 →
CAA**3617AM*+ furnace: PG80VTLB48070B**AHRI reference: 21564645517.008.10109002.06EPA 3959174 →
CAA**3617AM*+ furnace: PG80VTLB48090B**AHRI reference: 21564647917.008.10109002.08EPA 3959199 →
CAA**3617AM*+ furnace: PG95MSUA48060B**AHRI reference: 21564667817.007.80109002.06EPA 3959430 →
CAA**3617AM*+ furnace: PG96VTAB48060B**AHRI reference: 21564684417.008.10110002.06EPA 3959616 →
CAA**3617AM*+ furnace: PG96VTAB48080B**AHRI reference: 21564687217.008.10109002.06EPA 3959640 →
CAA**3717AM*+ furnace: PG96VTAB36060A**AHRI reference: 21564760817.008.10111002.08EPA 3960055 →
CAA**3717AM*+ furnace: PG96VTAB48060B**AHRI reference: 21564763417.008.10111002.08EPA 3960082 →
CAA**3717AM*+ furnace: PG95MSUA36040B**AHRI reference: 21564743617.007.80111002.08EPA 3960366 →
CAA**3717AM*+ furnace: PG95MSUA48060B**AHRI reference: 21564746317.007.80110002.10EPA 3960383 →

Sources and documentation

The table uses public EPA ENERGY STAR data. AHRI references are reported by EPA and have not been independently checked with AHRI. Source records do not establish availability, installation suitability or rebate eligibility.

No manufacturer manual has been matched to this model.

Collection method, revision history and known limitations →