MDV / AIR-SOURCE HEAT PUMP

MOD33-24HFN1-MT0W

MCD series · MS11M series · MSAB series · MSAG series · MSEP seris · MTI series · MUE series · MVC SERIES

8 published source records · source checked Sep 21, 2026

SEER2 range18–22BTU/Wh
HSPF2 range8.1–11.2BTU/Wh
Cooling capacity21,600–24,000BTU/h

Each efficiency range summarizes published EPA records for MOD33-24HFN1-MT0W. The highest SEER2 and HSPF2 may belong to different combinations. Open a source record below to see its ratings and the scope of its component information.

Model patterns and component strings are preserved exactly. How to read model patterns and combinations →

Heating performance & equipment details

Ranges include the 8 published source records for this model. Values in different rows may describe different configurations. Open an individual record to compare values from the same test configuration.

Reported fieldValue / rangeRecords supplying it
SEER2 · BTU/Wh18–228 / 8
EER2 · BTU/Wh11.7–148 / 8
HSPF2 · BTU/Wh8.1–11.28 / 8
Cooling capacity · BTU/h21,600–24,0008 / 8
Heating capacity at 47°F / 8.3°C · BTU/h21,600–26,0008 / 8
Heating capacity at 17°F / −8.3°C · BTU/h14,200–20,0008 / 8
Heating capacity at 5°F / −15°C · BTU/h12,600–20,0008 / 8
COP at 5°F / −15°C1.75–2.38 / 8
Equipment / loop typeHP - Mini or Multi Split · HP - Split System8 / 8
Refrigerant / source-reported GWPR-410A (GWP:2088)8 / 8
Compressor stagingContinuously variable8 / 8
Connected capabilityNo8 / 8

47°F = 8.3°C; 17°F = −8.3°C; 5°F = −15°C. COP is dimensionless. These are reported rating points, not a prediction of a particular home’s heat demand or operating limit.

Matched systems

Each row is one source record. The component column distinguishes listed combinations from outdoor-model ratings without an indoor configuration.

Indoor unit / required furnaceSEER2BTU/WhHSPF2BTU/WhHeating capacity at 5°F / −15°CBTU/hCOP at 5°F / −15°CRecord & comparison
MSEPD-24HRFN1-MU0WAHRI reference: 20636956122.0010.00155001.80EPA 2407655
MCD1-24HRFN1-MT0W(GA)Cold climate designationAHRI reference: 20733821821.509.70185002.20EPA 2407637
CS11M-23HRFN1-MT0WAHRI reference: 20854601221.508.50126001.75EPA 2732866
MUEU-24HRFN1-M(C)Cold climate designationAHRI reference: 20633012021.2010.30182002.20EPA 2407682
MSABE-24HRFN1-MU0WAHRI reference: 20764589821.009.00166001.92EPA 2407593
MSAG11D-23HRFN1-MU0WAHRI reference: 20636186721.008.50167001.90EPA 2407660
MTIU-24HWFN1-MCold climate designationAHRI reference: 20633013319.0011.20200002.30EPA 2407670
MVC-23HWFN1-MAHRI reference: 20774257818.008.10140001.90EPA 2410033

Sources and documentation

The table uses public EPA ENERGY STAR data. AHRI references are reported by EPA and have not been independently checked with AHRI. Source records do not establish availability, installation suitability or rebate eligibility.

No manufacturer manual has been matched to this model.