LG / AIR-SOURCE HEAT PUMP

KUSXA301A

KUSXA301A

8 published source records · source checked Sep 21, 2026

SEER2 range15.5–25BTU/Wh
HSPF2 range8.8–10.4BTU/Wh
Cooling capacity23,000–30,000BTU/h

Each efficiency range summarizes published EPA records for KUSXA301A. The highest SEER2 and HSPF2 may belong to different combinations. Open a source record below to see its ratings and the scope of its component information.

Model patterns and component strings are preserved exactly. How to read model patterns and combinations →

Heating performance & equipment details

Ranges include the 8 published source records for this model. Values in different rows may describe different configurations. Open an individual record to compare values from the same test configuration.

Reported fieldValue / rangeRecords supplying it
SEER2 · BTU/Wh15.5–258 / 8
EER2 · BTU/Wh11.7–15.28 / 8
HSPF2 · BTU/Wh8.8–10.48 / 8
Cooling capacity · BTU/h23,000–30,0008 / 8
Heating capacity at 47°F / 8.3°C · BTU/h26,000–34,0008 / 8
Heating capacity at 17°F / −8.3°C · BTU/h16,000–22,0008 / 8
Heating capacity at 5°F / −15°C · BTU/h24,000–34,0008 / 8
COP at 5°F / −15°C1.8–2.18 / 8
Equipment / loop typeHP - Mini or Multi Split · HP - Split System8 / 8
Refrigerant / source-reported GWPR-32 (GWP:675 | Lower GWP)8 / 8
Compressor stagingContinuously variable8 / 8
Connected capabilityNo8 / 8

47°F = 8.3°C; 17°F = −8.3°C; 5°F = −15°C. COP is dimensionless. These are reported rating points, not a prediction of a particular home’s heat demand or operating limit.

Matched systems

Each row is one source record. The component column distinguishes listed combinations from outdoor-model ratings without an indoor configuration.

Indoor unit / required furnaceSEER2BTU/WhHSPF2BTU/WhHeating capacity at 5°F / −15°CBTU/hCOP at 5°F / −15°CRecord & comparison
KNSCB301ACold climate designationAHRI reference: 21482653525.0010.40340002.10EPA 3544265
KNUJB301ACold climate designationAHRI reference: 21483792818.809.50340001.86EPA 3544272
KNSLA301ACold climate designationAHRI reference: 21558857518.209.80330002.00EPA 3629922
KNSLA301ACold climate designationAHRI reference: 21728490918.209.80330002.00EPA 4029106
LKMMA30B1+ furnace: LNA**060B1Cold climate designationAHRI reference: 21728494918.009.00320001.80EPA 4029089
LKMMA30B1+ furnace: LNA**080B1Cold climate designationAHRI reference: 21728495018.009.00320001.80EPA 4029092
LKMMA30B1Cold climate designationAHRI reference: 21644525715.708.80306001.80EPA 3891022
LKMMA24B1Cold climate designationAHRI reference: 21644526415.508.80240001.80EPA 3891025

Sources and documentation

The table uses public EPA ENERGY STAR data. AHRI references are reported by EPA and have not been independently checked with AHRI. Source records do not establish availability, installation suitability or rebate eligibility.

No manufacturer manual has been matched to this model.

Collection method, revision history and known limitations →