MPC024S4S-1P
M series · MMA series
13 published source records · source checked Sep 21, 2026
Each efficiency range summarizes published EPA records for MPC024S4S-1P. The highest SEER2 and HSPF2 may belong to different combinations. Open a source record below to see its ratings and the scope of its component information.
Model patterns and component strings are preserved exactly. How to read model patterns and combinations →
Heating performance & equipment details
Ranges include the 13 published source records for this model. Values in different rows may describe different configurations. Open an individual record to compare values from the same test configuration.
| Reported field | Value / range | Records supplying it |
|---|---|---|
| SEER2 · BTU/Wh | 18–22 | 13 / 13 |
| EER2 · BTU/Wh | 11.7–14 | 13 / 13 |
| HSPF2 · BTU/Wh | 8.1–11 | 13 / 13 |
| Cooling capacity · BTU/h | 23,000–24,000 | 13 / 13 |
| Heating capacity at 47°F / 8.3°C · BTU/h | 24,000–26,000 | 13 / 13 |
| Heating capacity at 17°F / −8.3°C · BTU/h | 16,000–20,000 | 13 / 13 |
| Heating capacity at 5°F / −15°C · BTU/h | 14,000–20,000 | 13 / 13 |
| COP at 5°F / −15°C | 1.8–2.3 | 13 / 13 |
| Equipment / loop type | HP - Mini or Multi Split · HP - Split System | 13 / 13 |
| Refrigerant / source-reported GWP | R-410A (GWP:2088) | 13 / 13 |
| Compressor staging | Continuously variable | 13 / 13 |
| Connected capability | No | 13 / 13 |
47°F = 8.3°C; 17°F = −8.3°C; 5°F = −15°C. COP is dimensionless. These are reported rating points, not a prediction of a particular home’s heat demand or operating limit.
Matched systems
Each row is one source record. The component column distinguishes listed combinations from outdoor-model ratings without an indoor configuration.
| Indoor unit / required furnace | SEER2BTU/Wh | HSPF2BTU/Wh | Heating capacity at 5°F / −15°CBTU/h | COP at 5°F / −15°C | Record & comparison |
|---|---|---|---|---|---|
MWMC024S4-1PAHRI reference: 207683500 | 22.00 | 9.90 | 15500 | 1.80 | EPA 2469782 → |
MWMC024S4-*PAHRI reference: 211034419 | 22.00 | 9.90 | 15500 | 1.80 | EPA 2470532 → |
MWMC024S4*AHRI reference: 210665606 | 22.00 | 9.90 | 15500 | 1.80 | EPA 2470692 → |
M33C024S4-1PCold climate designationAHRI reference: 207683517 | 21.50 | 9.60 | 18500 | 2.20 | EPA 2469778 → |
M33C024S4-*PCold climate designationAHRI reference: 211034437 | 21.50 | 9.60 | 18500 | 2.20 | EPA 2470525 → |
M33C024S4*Cold climate designationAHRI reference: 210665624 | 21.50 | 9.60 | 18500 | 2.20 | EPA 2470676 → |
MCFA024S4*Cold climate designationAHRI reference: 210665618 | 21.20 | 10.20 | 18200 | 2.20 | EPA 2469755 → |
MCFA024S4-2PCold climate designationAHRI reference: 207683511 | 21.20 | 10.20 | 18200 | 2.20 | EPA 2469780 → |
MCFA024S4-*PCold climate designationAHRI reference: 211034431 | 21.20 | 10.20 | 18200 | 2.20 | EPA 2470527 → |
MMDB024S4-2PCold climate designationAHRI reference: 207683506 | 19.00 | 11.00 | 20000 | 2.30 | EPA 2469791 → |
MMDB024S4-*PCold climate designationAHRI reference: 211034426 | 19.00 | 11.00 | 20000 | 2.30 | EPA 2470674 → |
MMDB024S4*Cold climate designationAHRI reference: 210665613 | 19.00 | 11.00 | 20000 | 2.30 | EPA 2470688 → |
MMA024SM4-*PAHRI reference: 212348045 | 18.00 | 8.10 | 14000 | 1.90 | EPA 2547919 → |
Sources and documentation
The table uses public EPA ENERGY STAR data. AHRI references are reported by EPA and have not been independently checked with AHRI. Source records do not establish availability, installation suitability or rebate eligibility.
No manufacturer manual has been matched to this model.
Collection method, revision history and known limitations →