Innovair / AIR-SOURCE HEAT PUMP

MOS09H2BM0A

MDH Series · MDL Series · MHW Series · MOS Series

5 published source records · source checked Sep 21, 2026

SEER2 range19.5–25.8BTU/Wh
HSPF2 range11–12.5BTU/Wh
Cooling capacity9,000BTU/h

Each efficiency range summarizes published EPA records for MOS09H2BM0A. The highest SEER2 and HSPF2 may belong to different combinations. Open a source record below to see its ratings and the scope of its component information.

Model patterns and component strings are preserved exactly. How to read model patterns and combinations →

Heating performance & equipment details

Ranges include the 5 published source records for this model. Values in different rows may describe different configurations. Open an individual record to compare values from the same test configuration.

Reported fieldValue / rangeRecords supplying it
SEER2 · BTU/Wh19.5–25.85 / 5
EER2 · BTU/Wh12.8–14.95 / 5
HSPF2 · BTU/Wh11–12.55 / 5
Cooling capacity · BTU/h9,0005 / 5
Heating capacity at 47°F / 8.3°C · BTU/h10,000–11,0005 / 5
Heating capacity at 17°F / −8.3°C · BTU/h7,900–9,3005 / 5
Heating capacity at 5°F / −15°C · BTU/h8,000–8,6005 / 5
COP at 5°F / −15°C2.17–2.365 / 5
Equipment / loop typeHP - Mini or Multi Split5 / 5
Refrigerant / source-reported GWPR-454B (GWP:470 | Lower GWP)5 / 5
Compressor stagingContinuously variable5 / 5
Connected capabilityNo5 / 5

47°F = 8.3°C; 17°F = −8.3°C; 5°F = −15°C. COP is dimensionless. These are reported rating points, not a prediction of a particular home’s heat demand or operating limit.

Matched systems

Each row is one source record. The component column distinguishes listed combinations from outdoor-model ratings without an indoor configuration.

Indoor unit / required furnaceSEER2BTU/WhHSPF2BTU/WhHeating capacity at 5°F / −15°CBTU/hCOP at 5°F / −15°CRecord & comparison
MHW09H2BHRBCold climate designationAHRI reference: 21572543825.8012.5080002.36EPA 3629941
MCO09H2BHRACold climate designationAHRI reference: 21723001822.1011.8080002.18EPA 4015756
MCS09H2BHRACold climate designationAHRI reference: 21722999221.6011.3083002.17EPA 4015732
MDH09H2MHWACold climate designationAHRI reference: 21572546019.7011.5083002.31EPA 3629962
MDL09H2MHWACold climate designationAHRI reference: 21572545719.5011.0086002.25EPA 3629960

Sources and documentation

The table uses public EPA ENERGY STAR data. AHRI references are reported by EPA and have not been independently checked with AHRI. Source records do not establish availability, installation suitability or rebate eligibility.

No manufacturer manual has been matched to this model.